Fieldpiece SM482V SMAN 4-Port Wireless Digital Refrigerant Manifold

(0 Reviews) Write a review

In stock

Description

Fieldpiece SM482V Specifications

Pressure
Sensor Type Absolute pressure sensors
Port Type 1 x 3/8″ (0.95 cm) and 3 x 1/4″ (0.64 cm) standard SAE male flare fittings
Pressure Range and Units 870 Psig (English), 60.00 Bar (Metric), 6.000 MPa (Metric), and 6000 kPa (Metric)
Negative Pressure Range and Units 29 inHg (English), 74 cmHg (Metric), 0.98 Bar (Metric)
Resolution 0.1 Psig
0.01 Bar
0.001 MPa
1 kPa
0.1 inHg
1 cmHg
Negative Pressure Accuracy 29 inHg to 0 inHg: ±0.2 inHg
74 cmHg to 0 cmHg: ±1 cmHg
0.98 Bar to 0 Bar: ±0.01 Bar
Pressure Accuracy 0 Psig to 200 Psig: ±1 Psig
200 Psig to 870 Psig: ±(0.3% of reading + 1 Psig)
0 Bar to 13.78 Bar ±0.07 Bar
13.78 Bar to 60.00 Bar: ±(0.3% of reading + 0.07 Bar)
0 MPa to 1.378 MPa: ±0.007 MPa
1.378 MPa to 6.000 MPa: ±(0.3% of reading + 0.007 MPa)
0 kPa to 1378 kPa: ±7 kPa
1378 kPa to 6000 kPa: ±(0.3% of reading + 7 kPa)
Maximum overload pressure 870 Psig (5998 kPa)
Units Psig, kPa, MPa, bar, inHg, and cmHg
Microns for Vacuum
Sensor Type Thermistor
Port Type 1 x 3/8″ (0.95 cm) and 3 x 1/4″ (0.64 cm) standard NPT male flare fittings
Range and Units 50 to 9999 microns of mercury (English)
6.7 to 1330 Pascals (Metric)
0.067 to 13.30 mBar (Metric)
50 to 9999 mTorr (Metric)
0.050 to 9.999 Torr (Metric, equivalent to mmHg)
Resolution 1 micron of mercury (below 2000 microns)
0.1 Pascal (below 250 Pascals)
0.001 mBar (below 2.500 mBar)
1 mTorr (below 2000 mTorr))
0.001 Torr (below 2.000 Torr)
Accuracy at 25 at C (77 at F) ±(5% of reading + 5 microns of mercury): 50 to 2000 microns
±(5% of reading + 1.0 Pascal): 6.7 to 266.0 Pascal
±(5% of reading + 0.010 mBar): 0.067 to 2.660 mBar
±(5% of reading + 5 mTorr): 50 to 2000 mTorr
±(5% of reading + 0.005 Torr): 0.067 to 2.000 Tor
Maximum Overload pressure 580 psig
Units Microns of mercury
Temperature
Sensor type Type K thermocouple(nickel chromium/nickel aluminum)
Jack Type 3 x Type K thermocouple
Range -50 to 257°F (-46 to 125°C), limited by the thermocouplespecification.
Display range is -95 to 999.9°F (-70 to 537.0°C)
Resolution 0.1°F (0.1°C)
Accuracy
(Shown accuracies are after field calibration)
±(1.0°F): -95 to 200°F
±(2.0°F): 200 to 999.9°F
±(0.5°C): -70 to 93°C
±(1.0°C): 93 to 537.0°C
General Specifications
Display size 5″ (12.7 cm) (diagonal)
Backlight Blue (adjustable duration)
Radio Frequency 2.4 GHz
Wireless Range 1000′ (305 m) line of sight. Distance decreases through obstructions
Data Port USB-C -For extracting logged data or updating firmware.
Battery 6 x AA (Battery life below based on alkaline type)
Battery life 405 hours typical (without vacuum, backlight, and wireless)
Low battery indication Icon displayed when the battery voltage drops below the operating level
Auto Shut off 30 minutes of inactivity (adjustable)
Operating environment 14 to 122°F (-10 to 50°C) at <75% RH
Storage temperature -4 to 140°F (-20 to 60°C), 0 to 80% RH (with battery removed)
Temperature coefficient 0.1 x (specified accuracy) per 1.8°F (14 to 64°F, 82 to 122°F), per°C (-10 to 18°C, 28 to 50°C)
Over range OL for pressure
– – – – for temperature
Weight 3.97 lbs (1.8 kg)
Water Resistant Designed to IP55
Refrigerants R11 R115 R290 R407A R414A R422A R438A R458A R600 R12 R116 R401A R407C R414B R422B R448A R500 R600A R13 R123 R401B R407F R416A R422CR449A R501 R601 R22 R124 R402A R407H R417A R422D R450A R502 R601AR23 R125 R402B R408A R417C R424A R452A R503 R744* R32 R134A R403B R409A R420A R427A R452B R507A R1233ZD R113 R236FA R404A R410AR421A R428A R453A R508B R1234YF R114 R245FA R406A R413AR421B R434A R454B R513A R1234ZE

Click here for complete specifications on the Fieldpiece SM482V

Reviews

There are no reviews yet.

Be the first to review “Fieldpiece SM482V SMAN 4-Port Wireless Digital Refrigerant Manifold”
Review now to get coupon!

Your email address will not be published. Required fields are marked *

Back to Top
Product has been added to your cart
Compare (0)